ClickCease Diesel Powered Portable Skid Mounted Enclosed Generators and… | Closed - MatchAwards

Diesel Powered Portable Skid Mounted Enclosed Generators and Maintenance

Status
Closed, the response deadline passed on Sep 3, 2025
Agency
United States Department of the Navy
Office
SILVERDALE, USA
Notice type
Solicitation
Solicitation number
N0040625QS563
NAICS
238210 - Electrical Contractors and Other Wiring Installation Contractors
PSC
6115 - GENERATORS AND GENERATOR SETS, ELECTRICAL
Set-aside
Total Small Business Set-Aside (FAR 19.5)
Posted
2025-08-29
Deadline
2025-09-03
Place of performance
Silverdale, Washington 98315, UNITED STATES

Description

Diesel Powered Portable Skid Mounted Enclosed Generators

Statement of Work

Strategic Weapons Facility Pacific (SWFPAC), Code SPB14

Scope of Work:  The contractor shall provide, unpack and deliver in-place two (2), enclosed Diesel Powered Portable Skid Mounted Generator-Sets with power cable connections to United States Coast Guard Airstation/SFO Port Angeles, 1 Ediz Hook Road, Port Angeles, WA 98362. Prior to delivery contractor shall remove and dispose of (2) currently installed 50kW generators. Contractor shall coordinate delivery, installation, connection and operational testing of (2) new generators with Government Point of Contact (POC). Contractor shall submit detailed specifications and recommended origninal equipment manufacturer (OEM) maintenance for proposed generators. Contractor shall provide 12 months of OEM recommended maintenance following installation and successful testing, to be performed on-site. Maintenance may be extended up to 1 time for an additional 12-month period.

Period of Performance:  Once awarded, contractor will provide equipment specified by this contract within 6 (six) months from award date.

Deliverables:

  1. Rating shall be 50 kW, three phase, four-wire, 480 VAC line voltage, 277 VAC phase voltage, with a continuous power factor of 0.8. 
  2. The load under normal conditions is approximately 18 kW. A single 7.5 horsepower three-phase sewage lift pump motor will be called upon intermittently as an addition to this normal load. 
  3. Contractor may recommend a diesel-generator rating lower than the recommended 50 kW @ PF=0.8 is viable to avoid unnecessary 'wet-stacking' of the diesel during times when the lift pump is not operating, i.e., 18 kW.
  4. Contractor shall provide connection cable compatible with transfer switch in Enclosure (1).
  5. Diesel-generator shall be able to start sewage lift pump motors directly across the line simultaneously without causing an unacceptable voltage drop to the system. The specific technical cut sheets for the sewage lift pump motors are attached as Enclosure (3).
  6. Diesel-generator shall have the capability to auto-start via an automatic transfer bus/switch for future capability.

  1. Contractor shall dispose of currently installed generators in accordance with all applicable federal and state regulation.