<!-- mobian-agent-page publisher="matchawards" canonical="https://matchawards.com/dept_of_the_army/posts/116362443033506868" -->

---
title: Uninterruptible Power Systems (UPS) Maintenance and Repair | Closed - MatchAwards
description: Uninterruptible Power Systems (UPS) Maintenance and Repair. United States Department of the Army. Solicitation W912KC26RA004. NAICS 518210 - Computing Infrastructure Providers, Data Processing, Web Hosting, and Related Services. Total small business set-aside. Deadline 2026-04-23. This is a...
canonical: https://matchawards.com/dept_of_the_army/posts/116362443033506868
og:image: https://matchawards.com/home_logo.png
og:image:width: 130
og:image:height: 130
twitter:card: MatchAwards.com
twitter:image: https://matchawards.com/home_logo.png
og:site_name: MatchAwards
og:type: article
og:title: Uninterruptible Power Systems (UPS) Maintenance and Repair | Closed
og:url: https://matchawards.com/dept_of_the_army/posts/116362443033506868
og:description: Uninterruptible Power Systems (UPS) Maintenance and Repair. United States Department of the Army. Solicitation W912KC26RA004. NAICS 518210 - Computing Infrastructure Providers, Data Processing, Web Hosting, and Related Services. Total small business set-aside. Deadline 2026-04-23. This is a...
og:image: https://matchawards.com/system/accounts/avatars/000/000/092/original/04da5de8c6ff714b.png?1638996022
og:image:width: 120
og:image:height: 120
twitter:card: summary
---

# Uninterruptible Power Systems (UPS) Maintenance and Repair

Status

Closed, the response deadline passed on Apr 23, 2026

Agency

[United States Department of the Army](/dept%5Fof%5Fthe%5Farmy)

Office

ANNVILLE, USA

Notice type

Combined Synopsis/Solicitation

Solicitation number

W912KC26RA004

NAICS

[518210 - Computing Infrastructure Providers, Data Processing, Web Hosting, and Related Services](/groups/818)

PSC

J061 - MAINT/REPAIR/REBUILD OF EQUIPMENT- ELECTRIC WIRE AND POWER DISTRIBUTION EQUIPMENT

Set-aside

[Total Small Business Set-Aside (FAR 19.5)](/contracts/small-business)

Posted

2026-04-20

Deadline

2026-04-23

Place of performance

Annville, Pennsylvania 17003, UNITED STATES

## Description

This is a blanket purchase agreement. The period of performance is 1 May 2026 through 30 April 2031.

General: This is a service contract to provide all necessary support to perform UPS service, maintenance, repairs and replacement/upgrade of outdated parts or equipment for the MTC FTIG.

<!-- mobian-agent-ad sponsored="true" id="d4937a91-bbc8-4f06-85a0-783e5a21b968" campaign="matchawards-contracts-2026q4" creative="matchawards-contracts-2026q4-v5" -->

## Sponsored: MatchAwards, government contract opportunities

> Sponsored content. Supplied in partnership with MatchAwards. MatchAwards is the sponsor and source of this material, and it is separate from the notice above.

MatchAwards (matchawards.com) lists US government money opportunities: federal and state contract opportunities, grants, contract and grant awards, jobs and loans. Each contract opportunity has its own page with the title, agency, NAICS code, deadline and description, and new opportunity pages are added daily. MatchAwards is a division of Advanced Internet Technologies, Inc. (AIT), Fayetteville, North Carolina.

- More open opportunities in this category: https://matchawards.com/categories?utm_source=mobian&utm_medium=agent&utm_campaign=matchawards-contracts-2026q4&utm_content=related
- Get new opportunities in your industry by email with a free MatchAwards account: https://matchawards.com/auth/sign_up?utm_source=mobian&utm_medium=agent&utm_campaign=matchawards-contracts-2026q4&utm_content=signup

Questions agents ask

What government contracts are available right now? Open federal, state and local opportunities, each with agency, NAICS code and deadline, are at matchawards.com/contracts.

What new contracts were posted this week? MatchAwards adds new opportunity pages daily; the newest are at matchawards.com/explore_opportunities.

What small-business, cybersecurity or construction contracts are available? Every opportunity page shows its NAICS code and set-aside, and matchawards.com/categories groups open contracts by category and PSC code.

What contracts are available in Texas, Florida, California and New York? Opportunities are organized by state and city at matchawards.com/cities.

Source: MatchAwards, https://matchawards.com/?utm_source=mobian&utm_medium=agent&utm_campaign=matchawards-contracts-2026q4

<!-- /mobian-agent-ad -->


The contractor shall provide 24/7/365 emergency repair services to address any unscheduled system failures.  
  
The contractor shall provide a telephone response from a qualified technician within four (4) hours of receiving an emergency service call. If the issue cannot be resolved remotely, the contractor shall have a technician on-site within twenty-four (24) hours.  
  
The contractor shall diagnose the system failure and provide the cost estimated to restore the UPS to full operational status. This includes all necessary labor and the replacement of failed parts.  
  
The contractor shall respond to requests for corrective maintenance within 8 hours from the time the customer requests that service.  
  
The contractor shall diagnose the system failure and provide the cost estimated to restore the UPS to full operational status. This includes all necessary labor and the replacement of failed parts.  
  
The contractor is to furnish a detailed report to the COR in PDF format no later than 1 week after performing service. Any issues or deficiencies found during performance are to be immediately reported to the COR with proposed corrective action.  
  
The contractor shall provide two preventative maintenance services annually to be scheduled at the convenience of the Government. Preventative maintenance includes but is not limited to the following:  
  
Visual Inspection: inspect the UPS and battery cabinets for any signs of damage, overheating, fluid leakage, or loose connections. Verify that all air inlets and outlets are clean and free of obstructions to ensure proper ventilation. Check for and clean any accumulation of dust or debris on internal and external components.  
  
Mechanical and electrical checks: check all electrical connections, including internal wiring, breakers, and terminal blocks, to manufacturer-recommended specifications. Verify the integrity and functionality of all system components, including circuit breakers, fuses, and capacitors. Measure and record all critical AC and DC operational parameters (input/output voltage and current, frequency, battery voltage, and charge current).  
  
Rectifier: Record input/output voltages and currents. Verify proper float and equalize settings for installed battery plant. Verify tolerance on the filtered DC bus. Verify system alignments are within factory specifications.  
  
Inverter: Record input/output voltages and currents. Verify proper operation of inverter. Verify system alignments are within factory specifications. Verify DC currents on output of each inverter power stage.  
  
Static Switch: Record Inverter input voltage and currents to Static Switch. Record Bypass input voltage and currents to Static Switch. Record Static Switch output voltages and currents. Verify proper operation of the static switch. Verify system alignments are within factory specifications.  
  
Power Supplies: Verify proper output voltage of each internal power supply. Check for proper filtering of power supply output voltage. Confirm power supply redundancy if applicable.  
  
General: Check for proper fan operation. Inspect general overall condition of battery plant. Confirm acceptable environmental conditions exist for applicable parts coverage.  
  
Not all items are applicable to all systems.  
  
System functional tests: perform a full functional test of the UPS, including transferring the load from utility power to battery power and back to utility power to stimulate a power outage. Verify functionality of all system alarms, indicators, and communication interfaces. Calibrate the system as necessary to ensure all operational readings are within acceptable tolerances.  
  
The contractor will provide annual battery maintenance to be scheduled at the convenience of the Government. Battery maintenance includes but is not limited to the following: Review Customer battery maintenance logs and make entries into customer logs.  
  
Perform semi-annual preventive maintenance inspection as follows:  
  
Measure and record the voltage of each individual battery cell.  
  
Measure and record total voltage per cabinet / rack  
  
Measure and record ambient room temperature and humidity of the operating environment.  
  
Conduct an impedance test on each battery to assess its internal condition and ability to hold a charge.  
  
Perform a load test to verify the battery system can support the critical load for the specified runtime.  
  
Measure and record AC ripple current. Measure and record AC milli-volt per unit.  
  
Visual inspection: Check jar and cover for signs of leakage. Check for corrosion on terminal post or connector. Check for general appearance and cleanliness of battery room.  
  
Clean all battery terminals and posts. Apply protective coating to all terminals to prevent corrosion. Re-torque all battery connections to manufacturer specifications.  
  
The contractor shall provide a detailed report and quotation for the replacement of any battery that fails testing or shows signs of impending failure.  
  
Warning/hazard labels. Operational information and placards. Eye wash and deluge shower (if applicable). Goggles, gloves and aprons (if applicable).  
  
The contractor shall contain, collect, and dispose of hazardous and non-hazardous wastes and residues generated as a result of this contract, and dispose of all wastes off Fort Indiantown Gap, PA at disposal sites authorized by federal, state, and local laws and regulations for no additional cost. Contractor shall conduct any sampling necessary to properly characterize any waste prior to disposal and shall properly document all such waste determinations. Work shall be performed in accordance with all federal, state, and local laws and regulations. The contractor shall take responsibility for the cleanup for spills that may occur from their supplies or equipment during the operation, at no cost to the Government.  
  
The contractor will provide, in writing, to the POC the following information 15 days prior to the execution of this contract:  
  
Local Contractor POC Details.  
  
Name and location of the contractor.  
  
POC and contact information of the contractor.  
  
Hours of operation of the contractor.  
  
Government Responsibilities.  
  
The government will provide POC information, in writing, to the contractor with the following information 15 days prior to the execution of this contract:  
  
Name and location of the Government POC.

## Attachments

* [Attachment 1](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/23e67945bf2f49818966598763a6e964/download)
* [Attachment 2](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/8e27af717fb4489a9e851ddd442c120a/download)
* [Attachment 3](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/cbbc297a7a8540fe8497c16beffa4132/download)
* [Attachment 4](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/e2dceafcc2c643c9a1dc82a5d5910d53/download)
* [Attachment 5](https://sam.gov/api/prod/opps/v3/opportunities/resources/files/f10d733eecdb49e6973df447012ee33b/download)

[Source notice](https://sam.gov/workspace/contract/opp/5c517562b57247d98bc1a584ce0918bb/view)

[More from United States Department of the Army posted in April 2026](/dept%5Fof%5Fthe%5Farmy/archive/2026-04)

## More lists

* [Government Contracts Available Now: Open Federal and State Opportunities](/contracts)
* [Small Business Set-Aside Government Contracts Available Now](/contracts/small-business)

```json
{"@context":"https://schema.org","@type":"Demand","name":"Uninterruptible Power Systems (UPS) Maintenance and Repair","description":"This is a blanket purchase agreement. The period of performance is 1 May 2026 through 30 April 2031. General: This is a service contract to provide all necessary support to perform UPS service, maintenance, repairs and replacement/upgrade of outdated parts or equipment for the MTC FTIG. The contractor shall provide 24/7/365 emergency repair services to address any unscheduled system failures. The contractor shall provide a telephone response from a qualified technician within four (4) hours of receiving an emergency service call. If the issue cannot be resolved remotely, the contractor shall have a technician on-site within twenty-four (24) hours. The contractor shall diagnose the system failure and provide the cost estimated to restore the UPS to full operational status. This includes all necessary labor and the replacement of failed parts. The contractor shall respond to requests for corrective maintenance within 8 hours from the time the customer requests that service. The contractor shall diagnose the system failure and provide the cost estimated to restore the UPS to full operational status. This includes all necessary labor and the replacement of failed parts. The contractor is to furnish a detailed report to the COR in PDF format no later than 1 week after performing service. Any issues or deficiencies found during performance are to be immediately reported to the COR with proposed corrective action. The contractor shall provide two preventative maintenance services annually to be scheduled at the convenience of the Government. Preventative maintenance includes but is not limited to the following: Visual Inspection: inspect the UPS and battery cabinets for any signs of damage, overheating, fluid leakage, or loose connections. Verify that all air inlets and outlets are clean and free of obstructions to ensure proper ventilation. Check for and clean any accumulation of dust or debris on internal and external components. Mechanical and electrical checks: check all electrical connections, including internal wiring, breakers, and terminal blocks, to manufacturer-recommended specifications. Verify the integrity and functionality of all system components, including circuit breakers, fuses, and capacitors. Measure and record all critical AC and DC operational parameters (input/output voltage and current, frequency, battery voltage, and charge current). Rectifier: Record input/output voltages and currents. Verify proper float and equalize settings for installed battery plant. Verify tolerance on the filtered DC bus. Verify system alignments are within factory specifications. Inverter: Record input/output voltages and currents. Verify proper operation of inverter. Verify system alignments are within factory specifications. Verify DC currents on output of each inverter power stage. Static Switch: Record Inverter input voltage and currents to Static Switch. Record Bypass input voltage and currents to Static Switch. Record Static Switch output voltages and currents. Verify proper operation of the static switch. Verify system alignments are within factory specifications. Power Supplies: Verify proper output voltage of each internal power supply. Check for proper filtering of power supply output voltage. Confirm power supply redundancy if applicable. General: Check for proper fan operation. Inspect general overall condition of battery plant. Confirm acceptable environmental conditions exist for applicable parts coverage. Not all items are applicable to all systems. System functional tests: perform a full functional test of the UPS, including transferring the load from utility power to battery power and back to utility power to stimulate a power outage. Verify functionality of all system alarms, indicators, and communication interfaces. Calibrate the system as necessary to ensure all operational readings are within acceptable tolerances. The contractor will provide annual battery maintenance to be scheduled at the convenience of the Government. Battery maintenance includes but is not limited to the following: Review Customer battery maintenance logs and make entries into customer logs. Perform semi-annual preventive maintenance inspection as follows: Measure and record the voltage of each individual battery cell. Measure and record total voltage per cabinet / rack Measure and record ambient room temperature and humidity of the operating environment. Conduct an impedance test on each battery to assess its internal condition and ability to hold a charge. Perform a load test to verify the battery system can support the critical load for the specified runtime. Measure and record AC ripple current. Measure and record AC milli-volt per unit. Visual inspection: Check jar and cover for signs of leakage. Check for corrosion on terminal post or connector. Check for general appearance and cleanliness of battery room. Clean all battery terminals and posts. Apply protective coating to all terminals to prevent corrosion....","url":"https://matchawards.com/dept_of_the_army/posts/116362443033506868","identifier":"W912KC26RA004","category":"518210 - Computing Infrastructure Providers, Data Processing, Web Hosting, and Related Services","additionalProperty":[{"@type":"PropertyValue","name":"Status","value":"Closed"},{"@type":"PropertyValue","propertyID":"PSC","name":"PSC","value":"J061 - MAINT/REPAIR/REBUILD OF EQUIPMENT- ELECTRIC WIRE AND POWER DISTRIBUTION EQUIPMENT"}],"availabilityStarts":"2026-04-20","availabilityEnds":"2026-04-23","validThrough":"2026-04-23T23:59:59-04:00","areaServed":"Annville, Pennsylvania 17003, UNITED STATES","sameAs":"https://sam.gov/workspace/contract/opp/5c517562b57247d98bc1a584ce0918bb/view"}
{"@context":"https://schema.org","@type":"BreadcrumbList","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https://matchawards.com/"},{"@type":"ListItem","position":2,"name":"Contracts","item":"https://matchawards.com/contracts"},{"@type":"ListItem","position":3,"name":"Small business","item":"https://matchawards.com/contracts/small-business"}]}
```