ClickCease Brand Name - Supervisory Control And Data Acquisition (SCADA)… | Closed - MatchAwards

Brand Name - Supervisory Control And Data Acquisition (SCADA) system

Status
Closed, the response deadline passed on May 2, 2025
Agency
United States Department of the Army
Office
JACKSONVILLE, USA
Notice type
Sources Sought
Solicitation number
W912EP25X161X
NAICS
237990 - Other Heavy and Civil Engineering Construction
Posted
2025-04-04
Deadline
2025-05-02
Place of performance
Florida 33493, UNITED STATES

Description

Sources Sought Synopsis

W912EP25X161X

Central Everglades Planning Project (CEPP) Contract 11C, EAA A-2 Reservoir Seepage Pump Station S-636, Palm Beach County, Florida

This announcement is to notify industry about the Government’s intent to incorporate a brand name product requirement in an upcoming construction project.  The product is the Supervisory Control And Data Acquisition (SCADA) system.  This product is being considered to be included in the specifications to build a seepage pump station.  This announcement seeks information from industry and will only be used for preliminary planning purposes.  THIS IS NOT A SOLICITATION FOR OFFERS AND NO CONTRACT SHALL BE AWARDED FROM THIS SYNOPSIS.  Respondents will not be notified of the results of the evaluation. 

The U.S. Army Corps of Engineers, Jacksonville District (SAJ) intends to include a product peculiar to only one brand name equipment manufacturer in its construction specifications under the authority 10 U.S.C. 3204(a)(1), Only one responsible source and no other supplies or services will satisfy agency requirements (FAR 6.302-1).  This notification is issued as a means of conducting market research to determine if the Government’s rational to require a SCADA system is justified.  This requirement is for a potential fiscal year (FY) 2026 award.  The project work consists of the construction of a seepage pump station at S-636 in Palm Beach Country, Florida for the  CEPP Contract 11C, EAA A-2 Reservoir program. 

The SAJ has a portfolio of ongoing ecological programs in South Florida to include CEPP.  These projects include hundreds of structures, pump stations, levees, and canals to control water movement throughout the area. All the elements are being tied, electronically, into the existing network of structures operated by the South Florida Water Management District (SFWMD). The system must operate consistently with other project features to maintain and/or improve existing levels of flood protection while enhancing environmental benefits to the system as a whole. The SFWMD Central Control System is a large, highly specialized system, which has been specifically designed for the unique requirements of remote operation of environmental restoration and flood control structures.  It is required to operate reliably under all weather conditions, specifically during severe storm events when travel is extremely hazardous. The system may be considered to be a life safety critical system, in that it has a direct impact on the life safety of individuals living within the SFWMD area during a storm event due to the ability to control flooding by operation of the various gates and pumps.

This is a new contract for the Central Everglades Planning Project (CEPP) Contract 11C, Everglades Agricultural Area (EAA) A-2 Reservoir Seepage Pump Station S-636.  The project is part of the Comprehensive Everglades Restoration Plan (CERP) with the objective to improve the quantity, quality, timing, and distribution of water flows to the central Everglades, Water Conservation Area 3 (WCA-3) and Everglades National Park (ENP). The lead federal agency is the U.S. Army Corps of Engineers, Jacksonville District and the South Florida Water Management District (SFWMD) is the local non-Federal sponsor for the project. As a requirement of the project, the contractor will be responsible for purchasing and installing a Supervisory Control and Data Acquisition (SCADA) System as part of the S-636 pump station, which consists of brand-name products.

The purpose of the Central Everglades Planning Project (CEPP) Everglades Agricultural Area (EAA) Reservoir Phase is to construct a 240,000-acre-foot EAA reservoir and 6,500 acre-foot stormwater treatment area, and integrate with A-1 FEB operations.

The S-636 (CNT11C) Project is designed to perform two primary functions:

•         Return seepage lost from the A-2 Reservoir to the C-623 (Inflow-Outflow canal)

•         Manage and maintain the C-636 (Seepage Canal) within an authorized range.

Project Description:

The work includes transportation of fill material, construction of cofferdams, dewatering, excavation, construction of a new pumping station structure, construction of a box culvert integrated with the pumping station, and incidental related work.

The new pumping station (S-636) structure has a pumping capacity of 250 CFS that consists of two 50 CFS, and two 75 CFS electric motor driven pumps. The station will include a backup generator to ensure continuous operation of the station in the event of commercial power interruption.

The new pumping station is required to be constructed in dry conditions and will include installation of a cofferdam system. Installation of mechanical, electrical, and telecommunication systems are incidental to the construction of the pumping station.

The SCADA system include the following major components; incidental items supporting the installation of these major components are shown indented just below the major component:

Remote Terminal Unit Gated Culvert

Equipment Name

Manufacturer

Model

Fire Alarm Control Panel

Honeywell

5820XL

Honeywell

N48PCI2L

Converter

Honeywell

LANSRLU1

Security Alarm Control Panel

Honeywell

VISTA-128FBP-KT18

APC Smart-Ups

APC

Transceiver, Aprisa SR+, UHF, Half-Duplex

4RF, USA

APSQ-N400-SSC-HD-22-ENAA

Transceiver, Aprisa SR+, VHF, Half-Duplex

4RF, USA

APSQ-N135-SSC-HD-22-ENAA

Controller, 6A, 12VDC, Solar, Charger

Morningstar

SS-6

Cable, Coaxial, Flexible, Low Loss, Solid Core

Times Microwave Sys.

LMR400

Connector, Coaxial, N-Male, Straight Plug, Lmr-400, Site Specific

Times Microwave Sys.

TC-400-NMH-D

Protector, Coaxial, Flange Mounted, DC Blocked, N-Female / N-Female

Polyphaser

IS-50NX-C2

Radio Modem, Integra-Tr, Site Specific VHF/UHF

CalAmp

242-40W8-XYZ*

Cable, Coaxial, Hybrid, Jumper, N-Male To SMA-Male, Rf Testing @ CF

Pasternack

PE3662-72

Cable, Serial, Hybrid, Rs-232 Motorola to Radio, Rj-45 To Db-9 Male, Non-Standard

Graybar

GRA031D1217-007

Base Model, RTU, ACE3600, 12V Ps, CPU 3610, Basic Frame

Motorola

7509

Frame Option, RTU, ACE3600, 3 I/O Slots

Motorola

V103

I/O Module, RTU, ACE3600, 32 Di Fast 24V

Motorola

V379

I/O Module, RTU, ACE3600, 16 Do Ee Relay 2A

Motorola

V616

Power Supply, RTU, ACE3600, Dc Power Supply 18-72V

Motorola

V251

CPU, RTU, ACE3600, 3640, Upgrade

Motorola

V446

I/O Module, RTU, ACE3600, 8Ai +/-20 Ma

Motorola

V318

Plug-In, RTU, ACE3600, RS-232

Motorola

V184

HMI Control Panel

Allen-Bradley

PanelView Plus 1900

"

Allen-Bradley

Compact Logix PLC

"

Motorola

ACE-3600

Cable, Coaxial, Flexible, Low Loss, Solid Core

Times Microwave Sys.

LMR-400-BULK

Connector, Coaxial, N-Male, Right Angle, Lmr-400

Times Microwave Sys.

TC-400-NMH-RA-SS

L-Foot, Solar Panel Rail, W/T-Bolt, Mill

Unirac

304001C

Panel, 345 Watt, Solar

Mission Solar Energy

MSE345SX5T

Rail, Solar Panel Racking 168-Inch, Clear

Unirac

310168C

Connector, Gnd, Lay-In, 4-14, #10, Tin

ILSCO/REXEL

GBL-4DBT

Nut, Hex, 3/8-16, 18-8 SS, 9/16 Acrflt

McMaster-Carr

92673A125

Nut, Hex, Ext Toothed Lk 1/4-20, 18-8 SS

McMaster-Carr

96278A511

Nut, Hex, Ext Toothed Lk 10-32, 18-8 SS

McMaster-Carr

96278A411

Plate, Backing, 2-13/16" C-C Spacing

Sterling Industry

Screw, Hex Hd, 1/4-20 X .75, 18-8 SS

McMaster-Carr

93190A540

Screw, Hex Hd, 3/8-16 X .3, 18-8 SS

McMaster-Carr

92186A636

Screw, Hex Hd, Serflg,10-32 X .75, 18-8

McMaster-Carr

97646A243

Spar, Left, Vert, Solar Panel Bracket

Sterling Industry

Spar, Right, Vert, Solar Panel Bracket

Sterling Industry

U-Bolt,3/8-16, 2-7/16 Id, Galv. Steel

McMaster-Carr

8862T29

Washer, Flat,1/4, 18-8 SS

McMaster-Carr

90107A029

Washer, Split, 3/8, 18-8 SS

McMaster-Carr

92146A031

Weldment, Triangle, Solar Panel Bracket

Sterling Industry

Core Mount SS Davit Sleeve DBI/Sala Model #8510110

DBI/SALA

8510110

Core Mount SS Davit Sleeve DBI/Sala Cap Model #8510827

DBI/SALA

8510827

Ladder Tie D-Bolt Anchorage Connector Model 417SS

MILLER

417SS

Hilti Hit-Re 500 V3 With 3/4" Has [304 316] 53/4" Embedment

HILTI

HIT-RE 500 V3

Face Mount SS Davit Sleeve DBI/Sala Model #8518348

DBI/SALA

8518348

Stainless Mini Rotary Latch Right Hand

EBERHARD

8-240 R

Gate Hinge Assembly Self Closing

D&D Technologies

Amphenol 90° Connector

Amphenol

MS3108E-14S-6S

3/8"-16 Pem Nut-SS Installed in the Side of Enclosure

PEM

CLS-0616-X

1/4" - 20 Pem Nut - SS Pressed In - From Bottom Face

PEM

CLS-0420-3

1/2" - 20 Pem Nut - SS Pressed In - From Bottom Face

PEM

CLS-0813-2 (No CLS-0813-3 LISTED)

Aluminum 1/4" Thick Hinge

McMaster-Carr

1609A2

Test Kit for Measuring Chloride, Sulfate and Nitrate Ions on Steel and Coated Surfaces

CHLOR*RID International Inc.

CHLOR*TEST CSN Salts

Test Kit for Identifying Amine Blush on Epoxy Surfaces

Elcometer

Amine Blush Check

Drawer Pull

B02011

Drawer Slides

B05051/B05052/B05053

Door Pull

B02201

Four Pin Disk Tumbler Lock

Illinois Lock Company

DUO A

Horn

Federal Signal Corporation

1N742

4A969 Weatherproof Box

Federal Signal Corporation

4A969

Anti-Seize

Bostik

Never Seez

1/8 To 1/2 Hp, Single-Phase, 60 Cycle, 120 VAC, Integral Gear Motor

Sumitomo

Chatsworth Universal Rack
W/ Base Insulators

Chatsworth

46053-515
10605-019

120VAC Rackmount Power Strip

APC

PDU-AP8632

Fiber Optic Inside Plant Patch Panel

Corning

CCH-02U/MMCCH LC

Fiber Optic Inside Plant Patch Panel

Corning

SM-CCH LC

Scada Switch

Cisco

Catalyst C9200L-24P-4X,
PWR-C5-600WAC

Scada Switch Wire Management

Chatsworth

30530-719

Scada Patch Panel 24 Port

Siemon

HD6-24

Enterprise Switch

Cisco

Catalyst C9200L-48P-4X
PWR-C5-1kWAC

SCADA Patch Panel

Siemon

HD6-48

KVM Rack Mount Console

Tripp Lite

B021-00017

Server 6TB

Salient

BL06T3B, 16CV

CCTV Switch

Fortinet

CDW part# 4105407

CCTV TVSS

DITEK

DTK-RM24NETS

It System Ups

APC

SMART-UPS Model SURTA2200RWXL2U

Ess System Ups

APC

SMART-UPS Model SURTA2200RWXL2U

Single Mode Fiber Optic Patch Panel - Corning 24 Pair.

Corning

Solara #20033-2, 20033-9, 20033-10

Solara

20033-2, 20033-9, 20033-10

Digital Shaft Encoder

Design Analysis Associates

H-3341 Water Log Series

Mounted Pump Cutoff Switches

Jerguson

Jerguson Model JDC1D
Jerguson Model JDC2D

Ultrasonic Level Sensors

Drexelbrook

USonic-R Series or equal.

Lightning/Surge: General
Line Noise Suppressing Isolation Transformers and Surge Suppressors.

Topaz Series 30 Ultra
Isolators or equal

Lightning/Surge: Power Supply
Line Noise Suppressing Isolation Transformers and Surge Suppressors.

Edco

HSP-121 or equal

Lightning/Surge Protection: Analog

Edco

PC 642 or SRA 64

Lightning/Surge Protection: Analog

Edco

SS64 series or equal

Lightning/Surge Protection: Analog

Edco

SLAC series or equal

Norton Utilities

Norton

Norton Utilities (latest version)

One (1) Dell Timbuk2 16" Carry Case

Dell

Dell Timbuk2 16" carry case

Aircable Wireless Serial Connector

Aircable

ACC1202
CC1302

ATI's Mobility® Radeon™ Hd3670 - 512Mb

ATI

HD3670

Dell Latitude E6410At6 Or Latest Version

Dell

E6410AT6

Microsoft Office (Latest Version)

Microsoft

Office

Dell Wireless 370 Bluetooth Module (2-1 + EDR)

Dell

Wireless 370 Bluetooth module (2-1 + EDR)

Rockwell Software's RSLogix5000 (Newest Version).

Rockwell Software

RSLogix5000
(newest version)

Pro Soft Modbus Master/Slave Communications Interface Module for Control Logix

Pro Soft

MV156-MCM

Allen-Bradley Stratix 5700

Allen-Bradley

Stratix 5700

Allen-Bradley Pv1900 PanelView +7 Series B Developed to Run on Windows 10 IOT Core.

Allen-Bradley

PV1900

Allen-Bradley PanelView Plus

Allen-Bradley

PB1900

Hoffman Consolet

Hoffman

Capwap Software

Pile Dynamics, Inc.

Case Pile Wave Analysis Program software

Testing Equipment

Pile Dynamics, Inc.

8G or PAX or equal

The O-Rings on a Quick Disconnect

Chemours

Viton

Simplex Compact Fuel Port

Simplex

Simplex Compact Fuel Port

Pump Bearings

Thordon

Shaft Couplings

Aquamet

Aquamet 22, Aqualoy 22, Nitronic 50 or approved equal

Shafts

Aquamet

Aquamet 22, Aqualoy 22, Nitronic 50 or approved equal

Shaft Bearing or Packing Box Sleeves

Aquamet

Aquamet 22, Aqualoy 22, Nitronic 50 or approved equal

O-Rings

O-Rings Buna-N or Viton or approved equal

Epoxy Coating

Chesterton

Chesteron ARC Epoxy coating.

Dynamic Analysis Model Program

Ansys, Cosmos/M, or equivalent

625kW Tier 4, Diesel Generator

Power Secure

Tier 4

Total Current Estimated Cost

$732,319.65

A number of contractors are sufficiently qualified to assemble the system, and a large number of suppliers sell the major components. However, the major components themselves are only manufactured by a single source. The government would incur substantial duplication of cost if non-standard major components from other manufacturers were allowed. These additional costs occur in several areas:

a.       Operator Training. Operators are currently trained to operate the Central Control System with its standardized major components. Substitution of non-standard major components into the Central Control System will substantially increase the training time necessary for the operator to become proficient. Operating a variety of diverse major components also decreases productivity and increases probability for error.

b.       Maintenance Technical Training. Maintenance technicians are currently trained to repair and maintain the standardized components of the Central Control System. Allowing non-standard major components to be installed in the system would result in substantial increases in the training required for each technician to be fully trained on each diverse make of a major component. Frequently, this training is conducted only at out-of-area facilities and would result in TDY and training costs. Non-standard equipment would also decrease the efficiency in which a major component is repaired, as technicians would have less experience on a particular make of major equipment than they do on the standardized major equipment.

c.       Spare Parts Stockage. Spare parts are currently stocked for the standardized major components of the Central Control System. These spare parts are a major investment for the government. Allowing non-standard major components to be installed would require an exponential increase in the number of spare parts required and thus an exponential increase in the space required and government investment in supplies. Space and money limitations would result in non-stockage of many items, which would dramatically increase part non-availability. This could be a critical problem during normal operations and a potential catastrophic problem during severe storm events.

d.       System testing and reliability. The Central Control System has been specifically designed to incorporate certain standardized major components. These components have been selected as a result of extensive industry research, have been exhaustively tested, and have been found to be reliable and dependable in many prior installations. Installation of non-standard major components would incur increased costs due to lack of testing of the component as part of the Central Control System. An individual non-standard component may perform well in another application, but it could interface poorly with the overall Central Control System due to interoperability problems. A non-standard component may also perform well on initial installation, but then fail due to the rigorous environmental conditions it is subjected to or due to poorer quality than the standard item.

e.       Increase down time due to no interchangeability of major components. Currently, individual components of major components may be interchanged between structures to keep critical structures operating. The use of non- standard parts will increase costs, as individual components of the major components will not be interchangeable. If a part is not in stock and has to be ordered, it could take several days for the control system to be repaired at an individual structure. During this time, additional costs will be incurred by the government, as an operator will have to be based on site or drive out to the site to operate the structure.

f.        Potential property destruction and civilian deaths due to non-availability and non-interchangeability of the system during storm events. SFWMD depends on the Central Control System to operate a large number of structures re