Description

Product Description
AIR FILTRATION SYSTEM REQUIREMENTS (VENTILATED ENCLOSURE/PAINT BOOTH)


Many ventilation systems exist and could potentially be used to control the Cr(VI) hazard during aviationmaintenance processes.Selection should be done in collaboration with Industrial Hygiene and Safety professionals to ensure the ventilation system meets minimum design criteria.


Defense Centers for Public Health-Aberdeen recommends the following minimum design criteria:


• American Conference of Governmental Hygienists (ACGIH)® Industrial Ventilation Manual Figure VS-75-01 Large Paint Booth: Minimum cross-sectional velocity of 75 feet per minute (fpm) for a large deep booth with a cross-sectional area greater than 150 square feet (ft2). Airless electrostatic and high velocity low pressure spray paint operations require an air velocity of only 60 fpm.


• ACGIH® Industrial Ventilation Manual Figure VS-80-01 Abrasive Blasting Room: Cross-sectional velocity range of 60-100 fpm.

• American National Standards Institute/American Society of Safety Professionals (ANSI/ASSP) Z9.4-201 I (R2021): Requires a cross-sectional velocity of 80 fpm.


Exhaust System
- 18,000 Cubic Feet per Minute or higher to achieve ACGIH recommended TLVs
- Must verify accurate testing and sampling data that system will provide clean air below the ACGIH TLVs of 0.0002mg/m3
- Exhaust air to be “RETURNED TO BUILDING” as per ANSI Z9.7 (NO ADDITIONAL VENTILATION REQUIREMENTS TO EXISTING STRUCTURES)
- Multi-stage Particulate filtration exceeds the National Emission Standards for Hazardous Air Pollutants (NESHAP) 319


Enclosure
- Enclosure must be Cross Draft Negative
- Material NFPA 701 Compliant
- Recommend size: 10’H X 18’W X 45”L (based on hangar size and unit requirements)


Fire Suppression
- Dry Chemical to protect both the enclosure and exhaust
- Pre-engineered meeting NFPA 17 Standard for Dry Chemical extinguishing

Replacement Filters 

- 18 Month Supply 

Lighting 

- Eight (8) Lights: 10,000 lumens per light

Warranty
- 5-year warranty