SMALL BUSINESS SET-ASIDE FOR HIGH-TEMPERATURE GAS HUMIDIFICATION SYSTEM
- Status
- Closed (archived notice)
- Agency
- United States Department of the Army
- Office
- ADELPHI, USA
- Notice type
- Combined Synopsis/Solicitation
- Solicitation number
- W911QX21Q0209
- NAICS
- 334512 - Automatic Environmental Control Manufacturing for Residential, Commercial, and Appliance Use
- PSC
- 6685 - PRESSURE, TEMPERATURE, AND HUMIDITY MEASURING AND CONTROLLING INSTRUMENTS
- Category
- Test & Measurement Supplies (5.4)
- Set-aside
- Total Small Business Set-Aside (FAR 19.5)
- Posted
- 2021-08-23
- Deadline
- 2021-08-27
- Place of performance
- Aberdeen Proving Ground, 21005
Description
The contractor shall provide one (1) turn-key high-temperature gas humidification system that meets or exceeds the following requirements: The system shall be capable of humidifying air from one (1) to 100.0 % relative humidity (%RH), with an accuracy of five percent (5%) RH or better. The system shall be capable of flowing humidified air at temperatures from ambient to 150 degrees Celsius (ºC) or higher, with an accuracy of five degrees Celcius (5ºC) or better. The system shall be capable of flowing humidified air from one (1) to two (2) Liters per minute or higher, with an accuracy of five percent (5%) of the reading or better. The system shall produce humidified air at output pressures of nine (9) bar or higher with variable output pressure option with an accuracy of 0.25 bar or better. The system shall have an external humidity sensor allowing for control of humidity in a separate chamber. The system shall be capable of accepting compressed air input up to 125 pounds per square inch, actual (psia) through a ¼-inch quick-connect, Swagelok compression fitting, or National Pipe Thread (NPT) connector. The system shall be capable of accepting deionized water at supply pressures up to 35 psia through a ¼-inch quick-connect, Swagelok compression fitting, or NPT connector. The system shall output humidified air through a ¼-inch Swagelok compression fitting or NPT connector. The system shall be capable of remote control and digital output of system settings through a RS232, RS485, or RJ45 connection. The system shall be mountable with appropriate mounting brackets for laboratory setupContacts
- Shanna Dellinger
- Brianna Murphy
Email and phone are in the source notice.
More from United States Department of the Army posted in August 2021