Bulk Oil/Coolant Storage & Dispenser System
- Status
- Closed, the response deadline passed on Jul 30, 2026
- Agency
- United States Department of the Air Force
- Office
- MINOT AFB, USA
- Notice type
- Combined Synopsis/Solicitation
- Solicitation number
- FA452826QSP03
- NAICS
- 332420 - Metal Tank (Heavy Gauge) Manufacturing
- PSC
- 5430 - STORAGE TANKS
- Category
- Construction Related Materials (4.1)
- Set-aside
- Total Small Business Set-Aside (FAR 19.5)
- Posted
- 2026-07-28
- Deadline
- 2026-07-30
- Place of performance
- Minot AFB, North Dakota 58704, UNITED STATES
Description
The Government is soliciting quotes for a modular fluid storage and dispensing system (delivery only) that meets the essential characteristics outlined in the attachments. The required system must fit within a 12’W x 9’D x 10’H footprint, operate entirely on facility compressed air, and secure four (4) 120-gallon aluminized steel tanks (3 Black for oil, 1 Blue for coolant).
The system must accommodate three different types of oil and one coolant. Key functional requirements include:
Two (2) pneumatic pumps: One AODD pump dedicated to the coolant line, and one Gear/Piston pump for the oil line.
An oil selector manifold: The oil pump must draw from a manifold connecting the three oil tanks, utilizing three 2-way isolation ball valves to select the desired fluid and prevent cross-contamination.
Two (2) 50ft hose reels: One reel dedicated to coolant and one shared reel for the three oil types.
A mandatory purge/flush line: The oil hose reel system must include a purge line or return valve, equal in diameter to the hose, to clear the line of residual fluid when switching between oil types.
Independent 10-micron filtration: Dedicated, independent 10-micron inline filters with isolation valves must be installed on both the oil and coolant lines.
Safety features must include color-change desiccant breathers, isolated sight gauges, drip pans, and a spill containment pallet capable of holding a minimum of 130 gallons. Quotes for "or equal" products will be evaluated provided they meet all specified characteristics.
Attachments
Contacts
- Sherry L. Platt
- Ted Arneson
Email and phone are in the source notice.