ClickCease Load Bank (A26-034) – United States Department of the Air Force | Closed - MatchAwards

Load Bank

Status
Closed, the response deadline passed on Feb 6, 2026
Agency
United States Department of the Air Force
Office
TINKER AFB, USA
Notice type
Presolicitation
Solicitation number
A26-034
NAICS
335311 - Power, Distribution, and Specialty Transformer Manufacturing
PSC
6150 - MISCELLANEOUS ELECTRIC POWER AND DISTRIBUTION EQUIPMENT
Posted
2026-02-02
Deadline
2026-02-06
Place of performance
S Coffeyville, Oklahoma 73145, UNITED STATES

Description

1.The 76th AMXG/567th is requesting utilization of funds for the purchase of one (1) Portable ResistiveLoad Bank.


2.The requested equipment item description / Specifications are outlined below.
a.Quantity of one (1) Portable Resistive Load Bank.
(1)230VAC L-N, 400VAC L-L, 3-Phase, 400 Hz
(2)6-Pin Aircraft Power Receptacle with Shield
(a)Must be supplied in accordance with (IAW) the requirements specified in DrawingLE409-0001.
(b)Suggested sources of supply (Anderson Airmotive part no. 3-498501 OR ITT CannonEA376 IAW dwg. LE409-0001).
(3)Load capacity of 100 kW or more.
(4)Switch to load in increments of 10 kW or less.
(5)Meter to display input frequency, volts, amps, watts.
(6)E/F interlock.
(7)4x BNC female connectors for monitoring of input power voltage, current, and frequency perphase with oscilloscope.
(8)Thermal Protection.
(9)Casters for ease of transport.
(10)Lifting pockets for loading/unloading with forklift.
(11)Noise level not to exceed 85 dB (A) IAW OSHA standard 29 CFR 1910.95.