30 CES - Pad Mount Transformers (1 of 2)

Status
Closed, the response deadline passed on May 30, 2025
Agency
United States Department of the Air Force
Office
VANDENBERG SFB, USA
Notice type
Combined Synopsis/Solicitation
Solicitation number
FA461025Q0041
NAICS
335311 - Power, Distribution, and Specialty Transformer Manufacturing
PSC
6120 - TRANSFORMERS: DISTRIBUTION AND POWER STATION
Category
Facility Related Materials (4.3)
Set-aside
Total Small Business Set-Aside (FAR 19.5)
Posted
2025-05-14
Deadline
2025-05-30
Place of performance
California 93437, UNITED STATES

Description

Funds are not presently available for this contract. The Government’s obligation under this contract is contingent upon the availability of appropriated funds from which payment for contract purposes can be made. No legal liability on the part of the Government for any payment may arise until funds are made available to the Contracting Officer for this contract and until the Contractor receives notice of such availability, to be confirmed in writing by the Contracting Officer.

Five (5) phase pad-mounted transformers shall have the following voltage ratings: 
 
•112.5 KVA, 208Y/120, 12 kV
•150 KVA, 480Y/277, 12 kV
•300 KVA, 480Y/277, 12 kV
•500 KVA, 480Y/277, 12.47 kV
•750 KVA, 480Y/277, 12 kV
 
In addition, the five phase pad-mounted transformers shall meet VSFB electrical requirements below: 
 
•All stainless-steel construction (includes tank, cabinet, base, radiators, fasteners, hinges, etc.),stainless-steel grade shall be 304L or 316L (if available).
•"Pentahead" cabinet locking mechanism/device.
•Dead-Front construction (HV-200A load break elbows with shield adapters).
•Externally clamped LV bushings with threaded copper stud for full load current below 2,100.amperes  - NEMA spades shall be provided per ANSI hole requirements.
•Radial feed or Loop feed
•Frequency: 60Hz.
•Windings: HV/LV copper
•Mineral Oil-filled (Non-PCB): Type FR-3 Fluid.
•Standard impedance.
•Mild steel high-voltage/low-voltage compartment barriers.
•Cooling fins.
•Proper grounding provisions.
•Dial type gauges for oil temperature, liquid level and pressure/vacuum.
•Bay-O-Net fuses & current-limiting fuses: properly sized  - additionally, the transformer shouldbe equipped with three spare fuses.
•Two-position "ON/OFF" load break primary switch
•5-position tap changer: (-5%, -2 ½ %, 0, +2 ½ %, +5%)
•Automatic pressure relief device mounted on the terminal compartment.
•Oil drain valve with sampling device, and an oil-fill/oil-level plug.
•Nameplate and NEMA safety labels: include a "UL Listed" symbol on ratings label andnameplate.
•Compliant with 2016 DOE Efficiency Standard.
•Four (4) lifting lugs.
 
•Entire exterior of the pad-mount transformer and terminal components shall be painted with aMunsell-Green, outdoor color-finish.
•Guaranteed to have an average coil winding temperature of 65°C rise over an average ambient airtemperature of 30°C when operated at rated voltage and load conditions.
•Provide DGA test to verify conformance to performance requirements as outlined in the latestrevisions of ANSI C57.12.00 and ANSI C57.12.90.