ClickCease Battery Install and Replacement | Closed - MatchAwards

Battery Install and Replacement

Status
Closed, the response deadline passed on Sep 19, 2024
Agency
United States Department of the Air Force
Office
KIRTLAND AFB, USA
Notice type
Combined Synopsis/Solicitation
Solicitation number
FA940124Q0035
PSC
6140 - BATTERIES, RECHARGEABLE
Set-aside
Total Small Business Set-Aside (FAR 19.5)
Posted
2024-09-12
Deadline
2024-09-19
Place of performance
Holloman AFB, New Mexico, UNITED STATES

Description

The Air Force has a requirement for the purchase of 12 sodium nickel battery modules to replace the existing
battery modules. In addition, one 200-amp power inverter and 27 additional electrical outlets are required for the
building. Contractor must remove and dispose of existing lead-acid batteries, provide Ethernet remote monitoring
capabilities, remove and dispose of existing power inverters and purchase and install replacement power inverters,
and purchase and install overhead electrical outlets located in the areas of the batteries and inverters.
Critical requirement to be met is that the battery system be 48 volts and provide 5 hours of power at the 120 amp
maximum load. Batteries must meet the following requirements: • Cycling Capability: 4.500 cycles (80% DOD)
• Battery energy density 100÷120Wh/kg, 150-190Wh/lt • Shelf life (> 20 years) • Temperature Immunity (-40 ÷
+60°C) • No gas emissions • No flammable materials • No fire/water flood reaction • 100% recyclable • NO
pollution materials • NO gas emissions
Power inverters must be one 200-amp and one 100-amp for the two required power inverters for the building.
Electrical outlets are to be 115V, 60 Hertz power.

Attachments

Source notice

More from United States Department of the Air Force posted in September 2024

More lists