Eaton PDU
- Status
- Closed (archived notice)
- Agency
- United States Department of the Air Force
- Office
- SCOTT AFB, USA
- Notice type
- Sources Sought
- Solicitation number
- F3S3162019AC01
- NAICS
- 335313 - Switchgear and Switchboard Apparatus Manufacturing
- PSC
- 6120 - TRANSFORMERS: DISTRIBUTION AND POWER STATION
- Category
- Facility Related Materials (4.3)
- Set-aside
- Total Small Business Set-Aside (FAR 19.5)
- Posted
- 2022-02-16
- Deadline
- 2022-02-18
- Place of performance
- Scott AFB, 62225
Description
QTY 8 PowerPak2 PDU - 150 kVA - True Front Access - Single Input - Main Input Circuit Breaker 250AF/225AT, 80% rated, 65kAIC - K20 Delta-Wye (DY1) 1-Output Copper, Temperature Rise,150C (Standard), Transformer Type: DOE2016 - Primary Input 480V - Secondary Output 208/120VAC - (8) 225AF/225AT Frame/Trip Rating Eaton Subfeed Breakers, 80% rate, 65kAIC - 200% neutral - Intelligent Power Monitoring - Local emergency power off (EPO) circuit - Interface board for building input alarms and Summary Alarm - WaveStar color touch display with remote communication interface via Modbus RTU protocol, Modbus TCP/IP or SNMP Dimensions: 42"W x 40"D x 84"H Weight: 2,800 lbs. 8 PowerPak2 PDU Startup Service 8 PowerPak2 PDU Commissioning LOT PDU Service Engineer travel time LOT Project Engineering Labor 1 FreightContacts
- Dominick Dockery
- TaShonna S Gordon
Email and phone are in the source notice.
More from United States Department of the Air Force posted in February 2022