Question 1: The RFI #3 below state that only conduit in Bldg. 40 can be reused. Every electrical drawing notes The DEISGN INTENT is to re-use the existing raceway where new devices are replacing devices in the same location. See the demo drawings for reference. Can this question be clarified further? Do can conduit be reused in all buildings as shown on the drawings? Answer: Conduit cannot be reused in all buildings; only conduit in Bldg. 40 can be reused as described in RFI #3 response. Question 2: There are conflicting notes in regards to the rough-in system for the low voltage systems. Is full conduit required even in accessible ceilings? Or is free air acceptable? Answer: Cabling can be run across j-hooks within accessible corridor ceiling spaces only. Contractor must submit coordination drawings showing proposed raceway system and run across j-hooks for VA review prior to installation.